Islanding Protection and Islanding Detection in Low Voltage CIGRE Distribution Network with Distributed Generations
Read full paper at:
http://www.scirp.org/journal/PaperInformation.aspx?PaperID=47104#.VGGHzWfHRK0
http://www.scirp.org/journal/PaperInformation.aspx?PaperID=47104#.VGGHzWfHRK0
Author(s)
Department of Energy Technology, Aalborg University, Copenhagen, Denmark.
Department of Electrical Engineering, Quaid-e-Awam University of Engineering, Science & Technology, Nawabshah, Pakistan.
Department of Electrical Engineering, Quaid-e-Awam University of Engineering, Science & Technology, Nawabshah, Pakistan.
Department of Electrical Engineering, Quaid-e-Awam University of Engineering, Science & Technology, Nawabshah, Pakistan.
Department of Electrical Engineering, Quaid-e-Awam University of Engineering, Science & Technology, Nawabshah, Pakistan.
Department of Electrical Engineering, Quaid-e-Awam University of Engineering, Science & Technology, Nawabshah, Pakistan.
Department of Electrical Engineering, Quaid-e-Awam University of Engineering, Science & Technology, Nawabshah, Pakistan.
The Power Quality
(PQ), security, reliability etc., are the prime objectives of the power system.
The protection is developed in such a way that it should be selective, fast,
reliable and the cost effective. The study about the islanding protection in
Low Voltage (LV) CIGRE distribution and networks like this has been proposed in
this paper. This is achieved by developing the protection against the short
circuit faults which might appear at the Medium Voltage (MV) bus. The
protection of the network with significant penetration of the Distributed
Generations (DGs) is a complicated process. The DG units which are directly
connected to the grid such as synchronous or induction generators contribute
large short power, whereas the DG units which are connected to the grid via
inverters carry small amount of the short circuit power. This creates the
problems in the protection of the network. If the proper protection
coordination measures have not been taken, it might cause the mal-function of the
protection devices which put the portion of the power network into the security
threats. The selection of the islanding protection devices in this paper is
made to protect the network against bi-directional currents at the time of
short circuit fault. The LV CIGRE distribution network will enter into
islanding if a fault is cleared at the MV bus by the proposed islanding
protection devices. It is therefore, essential to detect the islanding in the
CIGRE power network. The detection of the island in this network is another
major objective of this paper. The detection of the island is proposed by using the technique which is based
on the voltage phase angle difference. The
simulations are carried out by using DIgSILENT power factory software version
15.0.
KEYWORDS
Cite this paper
Mustafa Bhutto, G. , Ali, E. , Kumar, J. and Bhayo,
M. (2014) Islanding Protection and Islanding Detection in Low Voltage
CIGRE Distribution Network with Distributed Generations. Smart Grid and Renewable Energy, 5, 152-159. doi: 10.4236/sgre.2014.56014.
| [1] | Jenkings, N., Allan, R., Crossley, P., Kirschen, D. and Strbac, G. (2000) Embedded Generation (IEE Power and Energy Series 31), The Institution of Engineering and Technology, London. |
| [2] |
Ropp, M., Aaker, K., Haigh, J.
and Sabhah, N. (2000) Using Power Line Carrier Communications to Prevent
Islanding. Proceedings of 28th IEEE Photovoltaic Specialists
Conference, Anchorage, 15-22 September 2000, 1675-1678. http://dx.doi.org/10.1109/PVSC.2000.916224 |
| [3] |
Xu, W., Zhang, G., Li, C., Wang,
W., Wang, G. and Kliber, J. (2007) A Power Line Signaling Based
Technique for Anti-Islanding Protection of Distributed Generators—Part
I: Scheme and Analysis. IEEE Transactions on Power Delivery, 22,
1758-1766. http://dx.doi.org/10.1109/TPWRD.2007.899618 |
| [4] |
Wang, G., Kliber, J., Zhang, G.,
Xu, W., Howell, B. and Palladino, T. (2007) A Power Line Signaling
Based Technique for Anti-Islanding Protection of Distributed
Generators—Part II: Field Test Results. IEEE Transactions on Power
Delivery, 22, 1767-1772. http://dx.doi.org/10.1109/TPWRD.2007.899620 |
| [5] |
O’Kane, P. and Fox, B. (1997)
Loss of Mains Detection for Embedded Generation by System Impedance
Monitoring. 6th International Conference on Developments in Power System
Protection, Nottingham, 25-27 March 1997, 95-98. http://dx.doi.org/10.1049/cp:19970037 |
| [6] |
Usta, O., Redfern, M.A. and
Barrett, J.I. (1994) Protection of Dispersed Storage and Generation
Units against Islanding. Proceedings of 7th Electrotechnical Conference
on Mediterranean, Antalya, 12-14 April 1994, 976-979. http://dx.doi.org/10.1109/MELCON.1994.380938 |
| [7] | Affonso, C.M., Freitas, W., Xu, W. and da Silva, L.C.P. (2005) Performance of ROCOF Relays for Embedded Generation Applications. IEE Proceedings of Generation, Transmission and Distribution, 10 January 2005, 109-114. |
| [8] |
Ding, X., Crossley, P.A. and
Morrow, D.J. (2007) Islanding Detection for Distributed Generation.
Journal of Electrical Engineering & Technology, 2, 19-28. http://dx.doi.org/10.5370/JEET.2007.2.1.019 |
| [9] | Salman, S.K., King, D.J. and Weller, G. (2001) New Loss of Mains Detection Algorithm for Embedded Generation Using Rate of Change of Voltage and Changes in Power Factors. Proceedings of 7th International Conference on Developments in Power System Protection, Amsterdam, 9-12 April 2001, 82-85. |
| [10] |
Ding, X., Crossley, P.A. and
Morrow, D.J. (2007) Islanding Detection for Distributed Generation.
Journal of Electrical Engineering & Technology, 2, 19-28. http://dx.doi.org/10.5370/JEET.2007.2.1.019 |
| [11] | Cooper, C.B. (1989) Standby Generation Problems and Prospective Gains from Parallel Running. Proceedings of International Power System Protection Conference, Singapore, 1-6. |
| [12] | CIGRE Task Force C6.04.02 (2011) Benchmark Systems for Network Integration of Renewable Energy Resources, Version 7. |
| [13] | Mustafa, G., Bak-Jensen, B., Bak, C.L. and Pillai, J.R. (2013) Protection of Low Voltage CIGRE Distribution Network. Smart Grids and Renewable Energy, 4, 489-500. |
| [14] |
Medium Voltage Products, VD4 Medium Voltage Vacuum Circuit Breakers (12 -36 kV). www.abb.com eww141111lx |